EDGECELL-SPEC-B002

EDGECELL Cooling Door

Rear door heat exchanger · chilled-water rack cooling. Localized, energy-efficient cooling directly at the rack, engineered for HPC workloads and warm-water free cooling.

600–800 mm
3 widths
42U–52U
4 heights
337.5 mm
total depth incl. fans
6 × hot-swap
smart fan modules
EDGECELL Cooling Door — rear door heat exchanger

Cooling where the heat is — at the rack

The EDGECELL Cooling Door replaces the rear door of a standard IT rack with a chilled-water heat exchanger and a wall of six smart fan modules. Hot exhaust air is cooled before it leaves the rack, so the room stays neutral and the facility can run warm-water loops with free cooling for most of the year. Tool-less, hot-swappable components ensure maximum uptime and easy servicing, extending system lifetime.

Features

  • Supports 3rd-party racks
  • 3 widths (600 / 750 / 800 mm) and 4 heights (42U / 47U / 48U / 52U); additional sizes, colors and configurations on request
  • Total depth of device incl. fans 337.5 mm
  • Door opening angle > 90° with optional door stop
  • Optional sensors: air temperature, air humidity, water temperature, water flow, water pressure
  • Built-in leak detection sensors (optional)
  • Tool-less, hot-swappable fans, PSUs and main controller — no opening of the door required
  • 7" touch panel display with intuitive user interface
  • Connectivity: Ethernet, web interface, SNMP v3, Modbus TCP and RTU, Redfish and BACnet

Benefits

  • Front-accessible, quick-swap modular controller cassette for simplified maintenance and reduced service time
  • Compatible with direct-to-chip liquid cooling solutions for high-density computing applications
  • Modular adapter frame with a standardized design, easily configured to individual rack and site requirements
  • Quick-swap door hinging system enabling fast installation, removal and replacement of the RDHx door
  • Quick-swap coil mounting system designed for improved accessibility, servicing and replacement
  • Flexible fluid hose entry from either the top or bottom of the unit
  • Minimal planning requirements and reduced installation and commissioning time
  • Slim, space-efficient design suitable for installations where aisle or rear-rack clearance is limited

Data sheet EDGECELL-SPEC-B002

Key application / market positioningData center cooling in facilities with white space, warm water temperatures, increased air temperatures
Adapter frameApprox. 180 mm in depth; solid frame housing the heat exchanger and complete plumbing; no penetration of wetted material into the rack; increased safety against leaks
Top / bottom coverPanels with cutouts for flexible hoses and cabling
Size variationCustom
Return air filter · hose package · door switch · external temp sensorAccessories
Power suppliesDual — standard
Leak detectionOptional
Water sensorOptional; order corresponding hose package

* Water quality requirements must be maintained to avoid problems during operation. Usage of appropriate anti-corrosion and frost protection agents is recommended. ** Below 14 °C / 57 °F there is an increased risk of condensation. Water temperature must be maintained at 2 °C above dew point. It is recommended to use the cooling door in conjunction with a CDU to mitigate condensation.

Dual / redundant PSUStandard
Air humidity sensors12 (1 in each fan module)
Controller / fan / PSU swapTool-less quick swap
External communicationSerial (RS485), 2 × Gbit Ethernet
Communication interfacesModbus RTU, Modbus TCP, SNMP, Redfish, Web Browser, BACnet
Local interface / HMI7" touch panel display
Fan control · valve controlAutomatic
Valve type2-way
Hose kit connectionTri-Clamp
Standard colorsBlack Grey (RAL 7021), White (RAL 9003) textured
Fan modules6 smart fan modules with integrated sensors and fall-back control; hot-swappable without tools; access from aisle
Fan speed controlManual or automatic
ControllerSmart controller, hot-swappable without tools, access from aisle
Power suppliesUp to 2 wide-range PSUs, hot-swappable without tools, access from cold aisle
Coolant feedEgress for flexible hoses through cutouts at top or bottom panel
Control valve2-way ball valve, manual or automatic
Coolant flange at deviceMale BSPP 1" flat gasket (ISO 228-1) threaded flange
Operating temperature5–60 °C / 41–140 °F
Transport & storage temperature−40–85 °C / −40–185 °F
Normal operating pressure5 bar / 75 psi
Minimum burst pressure20 bar / 290 psi
Communication interfacesRS485, Ethernet, 2 digital inputs, 3 relay outputs
Communication protocolsModbus RTU, Modbus TCP, SNMP, Redfish, onboard web browser, BACnet, TCP/IP
Onboard sensors1 × supply air temperature + 1 × relative humidity in each fan module; 3 × inlet air temperature, 6 × outlet air temperature; 1 × fluid differential temperature, 1 × fluid differential pressure, 1 × air differential pressure
Optional sensorsLeak detection; door contact sensor kit; coolant sensors in hose package
pH7 – 9
Corrosion inhibitor(s)Required, as per ASHRAE TC 9.9
Sulfides< 10 ppm
Sulfate< 100 ppm
Chloride< 50 ppm
Bacteria< 1000 CFU/mL
Total hardness (as CaCO₃)< 200 ppm
Residue after evaporation< 500 ppm
Turbidity< 20 NTU
Glycol (propylene glycol) concentrationUp to 35%

EDGECELL selects and supplies a compliant coolant for your installation — see Products › Coolants.

750 mm
Width
2000 mm
Height
337.5 mm
Max depth
157.5 mm
Door depth
Part numberB-002-0001-BDX-OUT-FR-R1
Reference configuration750 mm × 2000 mm (42U)
General tolerancesISO 2768-1 m
Welded constructionEN ISO 13920:1996 Class B
Available widths600 mm · 750 mm · 800 mm
Available heights2000 mm (42U) · 2200 mm (47U) · 2250 mm (48U) · 2450 mm (52U)

Reference drawing for the 750 × 2000 mm configuration. Dimensional drawings (front, side, rear, top and isometric views) are included in the PDF spec sheet.

Everything needed for installation

🖼️

Extension frame

For installation onto the rack, with hinges, cutouts for hose egress and cabling at top and bottom, levelling feet and hose blankings.

🚪

Door with heat exchanger

Pre-assembled heat exchanger prepared for hose assembly at top or bottom, with filling/draining provisions, handle, door lock and keys.

🌀

Fan wall

6 hot-swappable fan modules, hot-swappable controller, pressure differential sensor, touch interface and 2 hot-swappable power supplies.

📘

Sensors & documentation

Onboard sensor set and user manual — provided as a download and within the packaging.

🧊

Size a Cooling Door for your racks

Send us rack dimensions, heat load per rack and your facility water temperatures. We will confirm the configuration, recommend a compatible coolant and prepare a quotation.